Proper treatment of make-up waste and boiler water is necessary to prevent scale, or other deposits, and corrosion within the boiler. The absence of adequate external and internal treatment can lead to operational upsets or total boiler failure. Where a choice is available, pretreatment external to the boiler is always preferred and more reliable than treatment within the boiler.
Obtain, and follow, instructions for feedwater treatment, prepared by a competent feedwater chemist. Do not experiment with homemade treatment methods or compounds.
Boiler Water Treatment. Boiler Water Treatment is critical for your boiler system. RMC will work with your team to ensure continuous operation of the production equipment; which will provide comfort heating, reduce costly downtime, and maximize energy efficiency. Our Benefits: Training on the proper use including training. Basic Boiler Principles HOT WELL DEAERATOR EXTERNAL TREATMENT MAKE UP RETURNED CONDENSATE WATER AND HEAT FEEDWATER WATER AND SOLIDS SATURATED STEAM EVAPORATED WATER Continuous blowdown to remove dissolved solids in boiler water Intermittent blowdown to remove suspended solids in boiler water. (See Instruction Supplement 1 in this manual) R, RH and RHC steam boiler models require four (4) gallons of feed water per hour for each 10 kW of electric heating capacity of the boiler. Lines should be of adequate size and meet local plumbing codes. Boiler feedwater treatment typically comprises a combination of several different processes, each designed to remove certain contaminants from raw make-up water or condensate return water. These processes can be divided into two parts: an upstream water-treatment system and a chemical treatment program. Temperature is held above 190° F there is a potential for feed water pump cavitation. – Temperature gauges fail, so holding the tank at 200ºF. – When the feed water pump comes on, the boiling point of water is reduced – Deareators use head pressure (1 psi for every 2.3 feet of height.
Representative samples of feedwater and boiler water must be analyzed frequently to ensure they are in specification. The following terms and guidelines are to be used in conjunction with the advice of a water treatment specialist.
Recommended Guidelines for Boiler Water Treatment
ANALYSIS | RECOMMENDED USAGE | COMMENTS |
pH Total Alkalinity Phosphates Total Hardness Chlorides Total Dissolved Solids Sulfites Specific Conductance Oxygen | 10-11 200-700 ppm 30-100 ppm 0-50 ppm 60-200 ppm 2000 ppm Maximum 20-30 ppm < 700 micro ohms cm < .007 mg/liter | Low pH promotes corrosion Low; promotes corrosion Prevents scale formation Prevents scale formation A measure of proper blow down High solids may cause surging A good oxygen scavenger A measure of proper blow down Prevents corrosion and pitting |
Use proper water treatment to prevent the buildup of scale on the boiler. After scale has built up on the walls of the boiler it is almost impossible to remove it from the boiler. The introduction of acids in the pressure vessel is thoroughly discouraged, since virtually any solution that will chemically attack the scale will also attack the boiler metal.
pH
The pH value of the boiler water is a number between zero and fourteen. Values below seven are acidic, seven is neutral, and values above seven are alkaline.
The pH factor is the most important factor influencing scale formation and the corrosive tendencies of boiler water. The pH should be maintained between a minimum of 10.5 and a maximum of 11.0 to prevent acidic corrosion of boiler tubes and plates, and to provide for the precipitation of scale forming salts before scale is deposited.
Below a pH of 5.0 the water is acidic enough to dissolve the steel boiler plates. Under these conditions the steel gradually becomes thinner and thinner until its destruction. At a pH between 5 and 9.4 pitting of shell plates will occur at a rate depending on the amount of dissolved oxygen in the boiler.
Dissolved Oxygen
Dissolved oxygen is caused by the solubility of atmospheric oxygen in the supply water. Aeration of the city water supply is frequently used to remove other noxious gasses. Efficient aeration results in saturation of the water with oxygen.
The majority of corrosion problems are directly related to the quantity of dissolved oxygen in the boiler water. Elimination of the corrosive effect of dissolved oxygen can be accomplished both directly and chemically.
Direct or mechanical removal of dissolved oxygen is accomplished through the use of a deaerator or by heating the water to a temperature above 180 degrees F. Heating the water can be done with a preheater or sparge tube installed in the return system.
Chemical deaeration is done through the introduction of specific chemicals in the boiler to react with the oxygen. The dissolved oxygen content should be maintained at a minimum but at no time should it exceed 0.007 mg/l.
Sulfites
Sodium sulfite is generally used for the chemical removal of dissolved oxygen within the boiler water. To assure the rapid and complete removal of the oxygen entering the boiler feedwater system the concentration of sulfite in the boiler must be maintained at a minimum of 20 PPM (parts per million).
Solids
Solids can be broken up into two categories: suspended solids and dissolved solids. Suspended solids are those which can be removed by filtration while dissolved solids are in solution with the water. The best test for the determination of solids content of the boiler water is through a conductance test.
The conductance value of boiler water varies by the various ionized salts present. The conductance can be used to measure the total dissolved solids in the boiler water and to serve as an accurate means of the control of solids through the use of blowdown.
Another test which is sometimes used as a gauge of solids is to measure the chloride present in the boiler water. The ratio of chlorides in the boiler water to that of the feed water can be used as a means to determine the amount of blowdown required. The chloride test is unsuitable for feedwater with low incoming concentrations and the concentrations in the feedwater must be averaged over time for accuracy.
High boiler solids will lead to foaming, priming, surging and carry over. These problems can be overcome by proper, daily blowdown of the boiler.
Alkalinity
The alkalinity of boiler water should be sufficiently high enough to protect shell and plates against acidic corrosion, but not high enough to produce carryover. A minimum value for alkalinity for adequate protection is 200 PPM.
Boiler Water Treatment Manual Pdf
High boiler alkalinity, which is in excess of 700 PPM, should be avoided. Values higher than this can lead to embrittlement of the steel.
Phosphates
Phosphates are used to react with calcium hardness in the boiler water. In order for this reaction to take place it is important to maintain a pH at a minimum value of 9.50. It is desirable to keep the concentration of phosphates in the water to 30 - 50 PPM in order for complete reaction of the phosphates with the calcium hardness entering the boiler through the feedwater.
Hardness
Boiler Water Treatment Test Kits
The hardness of water is caused by calcium and magnesium ions which will vary greatly throughout the country depending on the source of the water.
In boilers the hardness of the water can cause the formation of scale and sludge or mud. The hardness must be removed in the makeup water to the return system. Total hardness should not exceed 50 PPM.
Oils
Every effort should be made to prevent oils from getting into the boiler water. Oil causes foaming, or combines with suspended solids to form a sludge which can cause the overheating of boiler plates. If oil does get into the boiler, the boiler should be taken out of service immediately and thoroughly cleaned.
Pick your boiler, find a dealer near you, or contact us today to talk with a boiler expert about your needs.